rated insulation voltage 800V,rated opertating voltage up toAC 600V or 250V(DC),rated
operating currnet 6A-800A.It can be used in motors for unfrequent starting and interruption
with the function of the protection against overload,short circuit and undervolatge and
capable of preventing damage of circuits and supply units due to its protection devices
for over-current,short circuit and undervoltage.The MCCB complies with standard of
IEC60497-2&GB14048-2.According to its limit short circuit breaking capacity(lcu),the breaker
are classified into C-type(economical type with current trip-release on N pole closing and
opening with the other three poles),L-type(standard type),M-type(middle high breaking capacity
type) and H-type(high breaking capacity type).
Technical Speciffcation
| Type | ¡¡ | ¡¡ | Rated | Rated | Arcing | Ultimate | Rated | Operation | |
| Rated | No. | insulation | operating | over | short | service short | performance | ||
| current | of | voltage | voltage | distance | circuit | circuit | On | Off | |
| In(A) | Pole | Ui(V) | Ue(V) | (mm) | breaking | breaking | |||
| ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | capacity(KA) | capacity(KA) | |||
| GM1-63L | 6,10,16 | 3P,4P | 800V | 0 | 25 | 18 | 1500 | 8500 | |
| GM1-63M | 20,25,32 | 0 | 50 | 35 | |||||
| 40,50,63 | |||||||||
| GM1-100C | 10,16,20 | 0 | 25 | 18 | |||||
| GM1-100L | 25,32,40 | 0(¡Ü50£© | 35 | 22 | |||||
| GM1-100M | 50,63,80 | 0(¡Ü50£© | 50 | 35 | |||||
| GM1-100H | 100 | 0(¡Ü50£© | 85 | 50 | |||||
| GM1-225C | 100,125, | 380/660V | ¡Ü50 | 25 | 18 | 1000 | 7000 | ||
| GM1-225L | AV | ¡Ü50 | 35 | 22 | |||||
| GM1-225M | 160,180 | ¡¡ | ¡Ü50 | 50 | 35 | ||||
| GM1-225H | 200,225 | 250V/DC | ¡Ü50 | 85 | 50 | ||||
| GM1-400C | 225,250, | ¡¡ | ¡Ü50 | 35 | 25 | 1000 | 4000 | ||
| GM1-400L | 315,350, | ¡Ü50 | 50 | 35 | |||||
| GM1-400M | 400 | ¡Ü100 | 65 | 42 | |||||
| GM1-630C | 400,500, | ¡Ü100 | 35 | 25 | |||||
| GM1-630L | ¡Ü100 | 50 | 35 | ||||||
| GM1-630M | 630 | ¡Ü100 | 65 | 42 | |||||
| GM1-630H | ¡Ü100 | 100 | 65 | ||||||
| GM1-800M | 630,700, | ¡Ü100 | 65 | 42 | |||||
| GM1-800H | 800 | ¡Ü100 | 100 | 65 | |||||
Tripping characteristic
The thermodynamic ralease of the breaker provides the feature of inverse time-delay,
while the magnetic ralease is the instantaneous operation sa shown on table
(distribution circuit breaker)and table 2(motor protection circuit breakers).
|
Table1 |
¡¡ | ¡¡ | ¡¡ |
|
Rated current of release(A) |
Thermodynamic Release |
operational | |
|
(ambient temp:land+40¡æ marine+45¡æ |
current of | ||
|
1.05In(cold state) |
1.30In(heat state) |
magnetic | |
|
inoperative time(h) |
operative time(h) |
release(A) | |
|
6¡ÜIn¡Ü63 |
¡Ý1 |
¡´1 |
10-50In¡À20% |
|
63¡ÜIn¡Ü100 |
¡Ý2 |
¡´2 |
10In¡À20% |
|
100¡ÜIn¡Ü800 |
¡Ý2 |
¡´2 |
5-10In¡À20% |
|
Table 2 |
|||||
|
|
Thermodynamic Release |
operational | |||
|
Rated current |
(ambient temp:land+40¡æ marine+45¡æ |
current of | |||
|
of release(A) |
1.0In(cold state) |
1.20In(heat state) |
1.50In(heat state) |
7.2In(cold state) |
magnetic |
|
¡¡ |
inoperative time(h) |
operative time(h) |
operative time(h) |
operative time(h) |
release(A) |
|
10¡ÜIn¡Ü225 |
¡Ý2 |
¡´2 |
¡Ü4min |
4s |
12In¡À20% |
|
225¡ÜIn¡Ü400 |
6s | ||||
Outline and installation dimension